- 157 -
UMC22-FBPFieldBusPlug / Issue: 02.2008
V 6
Universal Motor Controller UMC22-FBP
Software version 4.0
Chapter 8.2.3~8
Par.
No.
Menu
No.
Menu point name Display:
7-segm.
Default Range Description / remark take over
21
(cont.)
3.7.19
-
3.7.18
Fault signal
always / delayed
DI2 = 1: faultless status ("released")
DI2 = 0: internal fault signal is set after
delay time independend of the motor
run/off status. After delay time inter-
nal fault signal is set motor stops.
Restart is possible only after fault
acknowledge
Remark:
The signals are monitored to the fi eld-
bus without delay.
during
motor off
Menü No. Display Delay time Menü No. Display Delay time
3.7.10
1 s 3.7.15 32 s
3.7.11
2 s 3.7.16 64 s
3.7.12
4 s 3.7.17 128 s
3.7.13
8 s 3.7.18 255 s
3.7.14
16 s
3.7.19 reserved
reserved
3.7.20
-
3.7.28
Motor off
always / delayed
DI2 = 1: motor: start is released, is not
stopped DI2 = 0: time starts indepen-
dend of motor run/off status. After
time delay motor is not longer released
or is stopped resp.“
Menü No. Display Delay time Menü No. Display Delay time
3.7.20 1 s 3.7.25 32 s
3.7.21 ... 2 s 3.7.26 64 s
3.7.22 4 s 3.7.27 128 s
3.7.23 8 s 3.7.28 255 s
3.7.24 16 s
3.7.29 reserved
reserved