- 158 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 8.2.3~9
Par.
No.
Menu
No.
Menu point name Display:
7-segm.
Default Range Description / remark take over
21
(cont.)
3.7.50
-
3.7.59
3.7.30
-
3.7.38
Fault signal
dependent /
delayed
DI2 = 1: faultless status
DI2 = 0: internal fault signal is not set
as long as the motor is not started,
delay time starts earliest with motor
start, internal fault signal stops motor
Restart is possible only after fault
acknowledge
during
motor off
Menü No. Display Delay time Menü No. Display Delay time
3.7.30
1 s 3.7.35 32 s
3.7.31 ... 2 s 3.7.36 64 s
3.7.32 4 s 3.7.37 128 s
3.7.33 8 s 3.7.38 255 s
3.7.34 16 s
3.7.39 reserved
reserved
3.7.40
-
3.7.48
Motor off
dependent /
delayed
DI2 = 1: motor is not stopped
DI2 = 0: motor start is not blocked, de-
lay time starts earliest with motor start,
after delay time motor is stopped.
Menü No. Display Delay time Menü No. Display Delay time
3.7.40 1 s 3.7.45 32 s
3.7.41 ... 2 s 3.7.46 64 s
3.7.42 4 s 3.7.47 128 s
3.7.43 8 s 3.7.48 255 s
3.7.44 16 s
3.7.49 reserved
reserved
3.7.50
-
3.7.59
Earth fault
monitoring
warning only
Menü No. Display Delay time Menü No. Display Delay time
3.7.50
1 s 3.7.54 16 s
3.7.51
2 s 3.7.55-
3.7.59
-
25 s
3.7.52
4 s
3.7.53
8 s