- 52 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.4~2
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Control
system
(digital
value if
different)
Control
Panel
Bus
connection
Accessible only via Control Panel (menu point: bu.co)!
Not a parameter, only for stand alone operation without fi eldbus. Allows to use the UMC22 without
FieldBusPlug, e.g. as Overload relay. Set and reset only via Control Panel.
- bu.oF
Stand alone operation:
Stand alone operation without fi eldbus, controlled by digital inputs and
Control Panel
- bu.on
Connected to the fi eldbus (= default):
Can be controlled via fi eldbus, via digital inputs or via Control Panel.
Bus fault
reaction
20
Accessible via control system or Control Panel (menu point: bu.Fr)!
All cases when UMC22 does not receive valid telegrams, either when control system or fi eldbus or
FieldBusPlug is out of order or interrupted.
Relays off
(0)
b.oFF
Relays off (= default):
Relay outputs of UMC22 will be switched off if a bus fault occurs.
Outputs
retain status
(1)
b.rEt
Outputs retain status:
According to the control function the relay outputs of UMC22 which are
used for motor control the retain their status if a bus fault occurs. For
Transparent mode this means that all 3 relays de-energize.
Change
password
Only accessible via Control Panel (menu point: PnEu)!
-
0001-
9999
Check-back
13
Accessible via control system or Control Panel (menu point: bA.ch)!
Auxiliary
contacts
(1)
bA.Au
Check-back via auxiliary contacts:
Check-back OK, when auxiliary contacts are closed 300 ms after start
Motor
current
(2)
bA.Cu
Check-back via motor current (= default):
Check-back OK, when current > 40 % of Set current is present 300 ms
after start
Simulation
(3)
bA.Si
Simulated check-back:
Check-back is simulated (e.g. for test without motor).
Remark:
Simulation is recommended only to be set via Control Panel, the control
system must only set Auxiliary contacts or Motor current to guarantee for
an operating check-back after next power on.
4.3.4 Parameter - Details in alphabetical order (continued)