- 53 - UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.4~3
4.3.4 Parameter - Details in alphabetical order (continued)
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Control
system
(digital
value if
different)
Control
Panel
Control
function
12
Accessible via control system or Control Panel (menu point: co.Fu)!
Transparent
(1)
c.trA
Control function Transparent (= default):
Direct access to DIs / DOs via fi eldbus
Overload
relay
(2)
c.oVL
Control function Overload relay:
Similar to overload relay.
Attention!
Normal signal on output DO0 is on and the connected contactor starts the
motor.
Direct starter
(3)
c.dir
Control function Direct starter:
Direct start of a motor for one direction of rotation
Reversing
starter
(4)
c.reV
Control function Reversing starter:
Reverse start of a motor for two direction of rotation
Star-delta
starter 1
(5)
c.Sd1
Control function Star-delta starter 1:
Star-delta start via 2 DOs
Pole-chan-
ging starter 1
(6)
c.Pch
Control function Pole-changing starter 1:
Pole-changing start for two-pole and dahlander motors
Actuator 1
(7)
c.Ac1
Control function Actuator 1:
OPEN and CLOSE Position via limit switch
Actuator 2
(8)
c.Ac2
Control function Actuator 2:
OPEN and CLOSE Position via limit and torque switch
Actuator 3
(9)
c.Ac3
Control function Actuator 3:
OPEN Position via limit switch, CLOSE Position via limit and torque switch
Actuator 4
(10)
c.Ac4
Control function Actuator 4:
OPEN Position via limit and torque switch, CLOSE Position via limit switch
Star-delta
starter 2
(11)
c.Sd2
Control function Star-delta starter 2:
Star-delta start via 3 DOs
Cooling time
10
Accessible via control system or Control Panel (menu point: ti.co)!
Cooling time simulates the cooling behaviour of the inoperating motor after tripping.
Remark:
During cooling time is running, RUN commands are not accepted. WARNING is monitored.
30-3600 s
(300-36000)
0030-
3600
30-3600 s
Steps via control system: 0.1 s: 30 s = 0,1 s x 300
Steps via Control Panel: 1 s: 30 s = 1 s x 30
Default value: 1200 resp. 0120 (=120 s)