- 55 - UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.4~5
4.3.4 Parameter - Details in alphabetical order (continued)
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Control
system
(digital
value if
different)
Control
Panel
DI0, DI1, DI2
Multi-function
input
05 / 07 / 21
Multi-function inputs offer additional possibilities to survey the motor and the production process
it is used for. Via the parameters DI0 Multi-function input, DI1 Multi-function input and DI2 Multi-
function input the inputs DI0, DI1 and DI2 can be parameterized as multi-function inputs with the
following functions:
Transparent (default): status is monitored only to the fi eldbus
Fault signal always / not delayed or delayed with 1 to 255 s:
The delay time starts whether the motor is running or not.
Fault signal dependent / delayed with 1 to 255 s:
The delay time starts only when the motor is running.
Motor off always / not delayed or delayed with 1 to 255 s:
The delay time starts whether the motor is running or not.
Motor off dependent / delayed with 1 to 255 s:
The delay time starts only when the motor is running.
Reset internal fault signal
Prepare emergency start: Reset of the thermal memory and of other faults.
Test Start without motor (no current check-back when started)