- 56 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.4~6
4.3.4 Parameter - Details in alphabetical order (continued)
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Control
system
(digital
value if
different)
Control
Panel
DI0, DI1, DI2
Multi-function
input
05 / 07 / 21
(continued)
Remark:
DI0, DI1 and DI2 can be parametrized via fi eldbus. Only DI2 can be parametrized via Control
Panel.
DI0: Check-back = Auxiliary contacts is dominating against Multi-function input.
DI0: can not be parameterized as Fault signal always / not delayed
(reason: compatibility to older versions)
000 P.000 Transparent (= default)
Input status is monitored only to the fi eldbus.
(correspondes to former parameter Fault input DI2 = Off)
001,
010
-
018
P.001,
P.010
-
P.018
Fault signal always / not delayed or delayed
DIx = 1: fault free status
DIx 0: Starts the delay time whether the motor is running or not. When
delay time has elapsed the internal fault signal is set und the
motor is stopped.
RUN commands will be only accepted when the fault has been
reset. Reset of fault is only possible if DIx = 1 again.
Remark:
DI0: Due to compatibility reasons - new UMC22 versions as replacement
in existing installations - DI0 = 1 is ignored and replaced by DI0 = 0.
Compatibility problems of the UMC22 Versions older than 3.31 consult
1.7.
delay
Command RUN FORWARD
Motor running
fault reset
internal fault signal
Signal on DI (closed circuit)
Parameter value Delay time Parameter value Delay time
001 resp. P.001 0 s 014 resp. P.014 16 s
010 resp. P.010 1 s 015 resp. P.015 32 s
011 resp. P.011 2 s 016 resp. P.016 64 s
012 resp. P.012 4 s 017 resp. P.017 128 s
013 resp. P.013 8 s 018 resp. P.018 255 s
1)
For DI2 compatible to the former Parameter "Fault input".