- 57 - UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.4~7
4.3.4 Parameter - Details in alphabetical order (continued)
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Control
system
(digital
value if
different)
Control
Panel
DI0, DI1, DI2
Multi-function
input
(continued)
05 / 07 / 21
002,
020
-
028
P.002,
P.022
-
P.028
Motor off always / undelayed or delayed
DIx = 1: Motor start is released, not stopped
DIx 0: Starts the delay time whether the motor is running or not. When
delay time has elapsed the motor is stopped. The internal fault
signal is not (!) set.
RUN commands will be only accepted when DIx = 1 again.
delay
Command RUN FORWARD
Motor running
Signal on DI (closed circuit)
Parameter value Delay time Parameter value Delay time
002 resp. P.002 0 s 024 resp. P.024 16 s
020 resp. P.020 1 s 025 resp. P.025 32 s
021 resp. P.021 2 s 026 resp. P.026 64 s
022 resp. P.022 4 s 027 resp. P.027 128 s
023 resp. P.023 8 s 028 resp. P.028 255 s
030
-
038
P.030
-
P.038
Fault signal dependent / delayed
DIx = 1: fault free status
DIx 0: Starts the delay time but only if the motor is running or is star-
ted. When delay time has elapsed the internal fault signal is set
und the motor is stopped.
RUN commands will be only accepted when the fault has been
reset. Reset of fault is only possible if DIx = 1 again.
delay
Command RUN FORWARD
Motor running
fault reset
internal fault signal
Signal on DI (closed circuit)
Parameter value Delay time Parameter value Delay time
034 resp. P.034 16 s
030 resp. P.030 1 s 035 resp. P.035 32 s
031 resp. P.031 2 s 036 resp. P.036 64 s
032 resp. P.032 4 s 037 resp. P.037 128 s
033 resp. P.033 8 s 038 resp. P.038 255 s