ENGINEERING STATION BUS (GO OSE)
1VLG5 00007 E 37
The data set defines what protection relay data is used in GOOSE service and sent to local
Ethernet subnetwork in a GOOSE message. The GOOSE control block links the data set and
its attributes to actual data.
GOOSE Control Block Attributes
– APPID – unique GoID in network
• Reserved value is ranging from
0x0000
to
0x3FFF
(Ed.1)
– MAC address
• Unique Multicast address per GoCB is recommended
• The allowed multicast address ranges from
01-0C-CD-01-00-00
to
01-0C-CD-01-01-FF
– GOOSE Control block name
– Data set definition
– VLAN ID
• The default value is 0x000; it should be configured to > 0
• Recommended values (as per IEC 61850-90-4) are ranging from
0x3E8 (1 000)
to
0x5E7
(1 511)
– VLAN priority
• The default value is 4 as per IEC 61850-8-1 (value range 0 …7)
– T
min
(ms)
• Maximum response time to data change
– T
max
(ms)
• Heartbeat cycle time in (the default value is 10 000 ms)
– ConfRev
• Its value increases when referenced data set becomes modified