ENGINEERING STATION BUS (GO OSE)
1VLG5 00007 E 37
The data set defines what protection relay data is used in GOOSE service and sent to local
Ethernet subnetwork in a GOOSE message. The GOOSE control block links the data set and
its attributes to actual data.
GOOSE Control Block Attributes
APPID – unique GoID in network
Reserved value is ranging from
0x0000
to
0x3FFF
(Ed.1)
MAC address
Unique Multicast address per GoCB is recommended
The allowed multicast address ranges from
01-0C-CD-01-00-00
to
01-0C-CD-01-01-FF
GOOSE Control block name
Data set definition
VLAN ID
The default value is 0x000; it should be configured to > 0
Recommended values (as per IEC 61850-90-4) are ranging from
0x3E8 (1 000)
to
0x5E7
(1 511)
VLAN priority
The default value is 4 as per IEC 61850-8-1 (value range 0 …7)
T
min
(ms)
Maximum response time to data change
T
max
(ms)
Heartbeat cycle time in (the default value is 10 000 ms)
ConfRev
Its value increases when referenced data set becomes modified