EasyManua.ls Logo

ABB UniGear Digital - Figure 103: PTP Global Dialog; Figure 104: PTP Version 2 (Transparent Clock) Global Dialog

ABB UniGear Digital
112 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENGINEERING ETHE RNE T
1VLG5 00007 E 79
3.5.10.2 Time Settings <Mandatory>
Time / PTP / Global
PTPv2 must be configured in case SMV (IEC 61850-9-2LE) is used.
Operation IEEE 1588 / PTP = ON
Configuration IEEE 1588 / PTP / PTP Version-Mode
V2-transparent-clock; used only to correct and forward PTP messages. The device cannot
become a PTPv2 master.
Figure 103: PTP Global dialog
Time / PTP / Version 2(TC) / Global
Profile Presets / Profile = Power - Defaults
Operation IEEE 1588 / PTPv2 TC
Delay mechanism = P2P (Peer to Peer)
Primary Domain = 0
Network protocol = IEEE 802.3
Syntonize = enabled to synchronize also local time
Power TLV Check = enabled
VLAN = 1
Figure 104: PTP Version 2 (Transparent Clock) Global dialog

Table of Contents

Other manuals for ABB UniGear Digital

Related product manuals