34
Megohmmeter Models 5050/5060
ScrollthroughtheresultsonthemaindisplaywiththeR-DAR-PI-DDbutton,oron
thesmalldisplaywiththeV/TIMEbutton.
Use R(t) when carrying out a ‘time-controlled test’ to scroll through the interval
measurement values saved at the sampling rate specied in SET-UP. These
valuesareavailableuntilanothermeasurementistakenortheselectorswitchis
turned.
When measuring high levels of insulation(>1G), it isadvisedthatthe “G”
guardterminalbeusedtoeliminatetheinuenceofsurfaceleakagecurrents.The
guardisconnectedbetweenthetwomeasurementcontactpoints,andthesurface
susceptibletosurfacecurrents,(e.g.dusty,dampcableortransformerinsulation).
Inthiscase,alligatorclipsarepreferabletotest-probesheldinthehand.
As soon as insulation measurement is stopped, the test circuit is automatically
dischargedusingtheinstrument’sinternalresistance.
5.3 Operation Examples
Connection diagram for measurement of low insulation (e.g. motor)
( )
FF 0.1A
380V - 10kA
5x20mm
110 - 230V
50/60 Hz
20 VA max
RS-232
2
nd
SMOOTHALARM
R(t)PRINT MEMMR
MEGOHMMETER
MODEL 5060
R-DAR-PI-DDPRINTMEM
V/TIME
START/STOP
1000V CAT III
2500V
G
OFF
M -1000V
M -2500V
M -5000V
M50-5000V
SET
-
UP
M -500V
+
-
M
Connection diagram for measurement of strong insulation
a)Exampleofamotor(reductionofcapacitivee󰀨ects)
( )
FF 0.1A
380V - 10kA
5x20mm
110 - 230V
50/60 Hz
20 VA max
RS-232
2
nd
SMOOTHALARM
R(t)PRINT MEMMR
MEGOHMMETER
MODEL 5060
R-DAR-PI-DDPRIN TMEM
V/TIME
START/STOP
1000V CAT III
2500V
G
OFF
M -1000V
M -2500V
M -5000V
M50-5000V
SET
-
UP
M -500V
+
G
-
M
w ww . . co m
information@itm.com1.800.561.8187