Site Preparation
7705 SAR-A Chassis Installation Guide 47
Warning:
To properly transport and relocate a 7705 SAR-A chassis, do the following:
disconnect power to the chassis by opening the disconnect devices
detach all cables from the chassis; remove the protective ground connection last
if the chassis is installed in a rack, carefully remove it from the rack
repackage the chassis in its original packaging or an appropriately sized shipping
container for relocation
The 7705 SAR-A systems powered by DC power should be installed in restricted
access areas, such as a dedicated equipment room or an equipment closet, in
accordance with Articles 110-16, 110-17, and 110-18 of the National Electric Code
ANSI/ NFPA 70.
To provide necessary stability, ensure that the equipment rack is bolted to the floor.
Ceiling brackets are useful to provide additional stability.
When wiring the unit, the chassis ground connection must always be made first and
disconnected last.
When mounting the chassis in a rack, ensure that the rack complies with all
requirements outlined in Chassis Location Requirements.
Maintain a clearance of at least 2.5 in. (6.4 cm) at the front of the 7705 SAR-A chassis
for cable management.
Maintain a clearance of at least 2 in. (5.1 cm) on each side of the 7705 SAR-A chassis
to ensure adequate airflow.
Maintain a clearance of at least 1.75 in. (4.4 cm) above and below the 7705 SAR-A
chassis to ensure adequate airflow.
The 7705 SAR-A includes a chassis ground stud on the mounting bracket attached to
the right-hand side of the chassis (when viewed from the front). The chassis ground
must be connected to the building ground, using either a direct connection or a ground
bus.
Electrostatic discharge (ESD) damage can occur if the 7705 SAR-A is mishandled.
Always wear an ESD-preventive wrist or ankle strap and always connect an ESD strap
to a nearby ground point that is connected to the site grounding point when working on
the 7705 SAR-A. Typical ground points include a properly grounded rack or work
bench.
The washers and nut used to secure the chassis ground wire on the ground stud must
only be used for that purpose.
Do not install equipment that appears to be damaged.
Install the 7705 SAR-A chassis in the equipment rack before installing SFPs.
Failure to comply with the equipment rack and chassis instructions as outlined in
Installation Locations and Chassis Location Requirements will cause thermal failure.