Installation Site Assessment
64 7705 SAR-A Chassis Installation Guide
Specific Characteristics of the Installation Site
Does the installation site exhibit characteristics that may require upgrade or repair?
Battery manufacturing
Mountains near a coastline
High humidity regions
Fossil fuel use, such as open fires used by locals for cooking or
burning farming byproducts
Table 11: Local Risk Factors (Continued)
Risk Factor Yes No
Table 12: Specific Characteristics of the Installation Site
Characteristic Yes No
Is the installation site in a room that is part of the building HVAC
system?
Does the installation site have protection to prevent ingress of
dust?
Does the installation site have protection to prevent ingress of
pollution?
Does the installation site have protection to prevent ingress of
humidity?
If outside air is brought in for ventilation, does it pass through a
filter?
If outside air is brought in for ventilation through a filter, is the
type and rating of the filter appropriate to the environmental
conditions?
Does the site have an air conditioner?
• Is the rating and capacity adequate for the space?
• Is there proper drainage of water from the air
conditioner?
Does the site have a dehumidifier?