System Specifications
50 7705 SAR-A Chassis Installation Guide
Notes:
1. Pollution degree is as defined in IEC 60950. Pollution Degree 2 applies where there is only non-conductive
pollution that might temporarily become conductive due to occasional condensation.
2. The AC operating voltage range applies only to the external AC power supply.
7705 SAR-A Power Consumption
Note:
1. Power consumption values include the power consumption of the pluggable optics (see Table 6).
Table 6 lists the maximum power consumption for the Alcatel-Lucent approved SFP, SFP+,
and XFP modules. Not all types are applicable to all chassis, adapter cards, and modules.
Contact your Alcatel-Lucent representative for information on SFP, SFP+, and XFP module
availability and applicability.
Earthquake Suitable for high-risk areas (Zone 4/California, for
short-duration disturbance)
Pollution degree
1
2
Rated voltage (DC) –48/–60 VDC
(–60 VDC is for various European countries)
Operating voltage range (DC) –40 to –75 VDC
Rated voltage (AC) 120/240 VAC
Operating voltage range (AC)
2
90 to 264 VAC
Acoustic noise level 7705 SAR-A is silent
Table 4: 7705 SAR-A Environmental Specifications (Continued)
Parameter Description
Table 5: Chassis Power Consumption
Description
1
Typical Power
(W)
Maximum Power
(W)
7705 SAR-A chassis with Ethernet and T1/E1 45 W 52 W
7705 SAR-A chassis with Ethernet only 43 W 50 W