142 Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Chapter 5   Safety Module Features
Table 43 shows the expected behavior of the muting status for test outputs 
TO2M and TO3M. Keep the following points in mind as well:
• When power is applied to the 5069-IB8S or 5069-IB8SK module, and 
T2 or T3 remains commanded off, the muting status defaults to on.
This bit operation is designed to help prevent erroneous muting 
instruction faults from the owner-controller. This bit status is not always 
the true indication of a burned-out lamp.
• If a muting lamp circuit is open when power is applied to the module, 
the condition is detected when the test output is commanded on.
• When a lamp burns out and is replaced, the fault (muting status bit) 
returns to the normal condition, independent of the state of the test 
output.
Table 43 - Muting Status Bit Operation
IMPORTANT Before checking the state of the corresponding muting status, be 
sure that the test output is commanded on. Once the test output is 
commanded on, a maximum time of 6 seconds is required for the 
module to detect a burned-out lamp.
Test Output 
Commanded 
State
Lamp 
Condition
Muting Status 
Bit
Description
ON Bad (open 
circuit)
0 Repair lamp.
ON Good 1 Normal condition. Lamp is operating properly.
OFF Bad (open 
circuit)
0 If lamp remains OFF after T1/T3 output cycled, repair 
lamp.
OFF Good 1 Normal condition.