Chapter 3
Interpret the Attribute Tables
134 Rockwell Automation Publication MOTION-RM003I-EN-P - February 2018
ID Access
Rule
Attribute B E F P V T Conditional Implementation
525 Get Flux Current Reference
- - Y Y Y
557 Set Flux Integral Time Constant
- - N N N
556 Set Flux Loop Bandwidth
- - N N N
558 Set Flux Up Control
- Y Y Y Y Ind Motor only
O-Enum
1 = Manual Delay (Y)
2 = Automatic Delay (Y)
559 Set Flux Up Time
- Y Y Y Y Ind Motor only
380 Set Flying Start Enable
- N - N -
381 Set Flying Start Method
- N - N - 0-Enum: V29
1 = Counter EMF (N)
2 = Sweep Frequency (N)
570 Set Frequency Control Method
- R - - - O-Enum
128 = Fan/Pump Volts/Hertz (Y)
129 = Sensorless Vector (Y)
130 = Sensorless Vector Economy (N)
498 Set Friction Compensation Sliding
- - Y Y Y4
499 Set Friction Compensation Static
- - Y Y4 Y4
500 Set Friction Compensation Viscous
- - Y Y Y4
826/421 Set Friction Compensation Window
- - Y - -
981/243 Get Guard Faults
- N N N N
980/242 Get Guard Status
- N N N N
280 Set Home Torque Threshold
- - N N - Vxx
281 Set Home Torque Time
- - N N - Vxx
1349 Set Induction Motor Magnetization Reactance
- N N N N Ind Motor only
1352 Set Induction Motor Rated Slip Speed
- Y N N N Ind Motor only
1351 Set Induction Motor Rotor Leakage Reactance
- Y Y Y Y Ind Motor only, V26/V27
1350 Set Induction Motor Rotor Resistance
- N N N N Ind Motor only
1348 Set Induction Motor Stator Leakage Reactance
- Y Y Y Y Ind Motor only, V26/V27
647 Set Inverter Overload Action
- Y Y Y Y O-Enum
1 = Current Foldback (Y)
128 = Reduce PWM Rate (N)
129 = PWM Foldback (N)
699 Set Inverter Thermal Overload User Limit
- Y Y Y Y
1338 Set Linear Motor Damping Coefficient
- N N N N Linear Motor only
2313 Set Linear Motor Integral Limit Switch
- N N N N Linear Motor only
1336 Set Linear Motor Mass
- N Y Y Y Linear Motor only
1337 Set Linear Motor Max Speed
- N Y Y Y Linear Motor only
801 Get Load Observer Acceleration Estimate
- - Y Y Y
806 Set Load Observer Bandwidth
- - Y Y Y

Table of Contents

Other manuals for Allen-Bradley ControlLogix

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ControlLogix and is the answer not in the manual?

Allen-Bradley ControlLogix Specifications

General IconGeneral
CommunicationEtherNet/IP, ControlNet, DeviceNet, DH+
I/O CapacityUp to 128, 000 I/O points (varies by configuration)
RedundancySupported (with specific modules)
Programming SoftwareRockwell Automation Studio 5000 Logix Designer
Operating Temperature0°C to 60°C (32°F to 140°F)
Programming LanguagesLadder Logic, Function Block Diagram, Structured Text, Sequential Function Chart
ModularityYes
CertificationsUL, CE
Processor TypeMultiple options available, including standard, safety, and extreme environment processors
Power SupplyMultiple options available, including standard and redundant power supplies with various voltage ranges (e.g., 24V DC, 120/240V AC)