148 Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
Appendix B Upgrade the Kinetix 350 Drive Firmware
7. Confirm the drive catalog number and firmware revision and click Finish
This ControlFLASH warning dialog box appears.
8. Click Yes (when ready).
The Progress dialog box appears and upgrading begins.
The drive four-digit status indicator changes to -PS- and scrolls IP address,
which indicates that upgrading is in progress.
After the upgrade information is sent to the drive, the drive resets and
performs diagnostic check-in, then it displays 350, -08-, and scrolls -00-
and the IP address.
9. Wait for the Progress dialog box to time out.
It is normal for this process to take several minutes.
IMPORTANT
Do not cycle power to the drive during this process or the firmware
upgrade is not completed successfully.