80 Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
Chapter 5 Configure and Start up the Kinetix 350 Drive System
Table 39 - Axis State Status Indicator
Status Indicator State
Off Off
Flash red/green Self test
Off Initialization - bus not up
Flashing green Initialization - bus up
Off Shutdown - bus not up
Flashing amber
(1)
(1) The axis and the drive define minor fault conditions. While a minor fault does not affect the drive status
indicator, it does affect the axis status indicator. When a minor fault condition is detected, a normally solid-
green status indicator indication changes to alternating red-green-red-green, a normally flashing green
status indicator indication changes to alternating red-off-green-off, and a normally flashing amber
indications changes to red-off-amber-off.
Shutdown - bus up
Off Pre-charge - bus not up
Flashing amber
(1)
Start inhibit
Flashing green
(1)
(2)
(2) The drive also defines alarm conditions. When an alarm condition is detected, a normally solid-green status
indicator indication changes to alternating amber-green-amber green while a normally flashing green
status indicator indication changes to alternating amber-off-green-off.
Stopped
Solid green
(1)
(2)
Stopping
Starting
Running
Tes ti ng
Flashing red
Aborting
Major faulted
Solid red
Aborting
Major faulted
Table 40 - Network State Status Indicator
Status Indicator State
Steady off Not powered, no IP address
Flashing green No connections
Steady green Connected
Flashing red Connection time-out
Steady red Duplicate IP
Flashing green and red Self-test