116 Using the High-Speed Counter and Programmable Limit Switch
The outputs shown in the black boxes are the outputs under the control
of the HSC sub-system. The mask defines which outputs can be
controlled. The high preset output or low preset output values (HPO or
LPO) define if each output is either ON (1) or OFF (0). Another way to
view this is that the high or low preset output is written through the
output mask, with the output mask acting like a filter.
The bits in the gray boxes are unused. The first 6 bits of the mask word
are used and the remaining mask bits are not functional because they do
not correlate to any physical outputs on the base unit.
The mask bit pattern can be configured only during initial setup.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1100 and is the answer not in the manual?

Allen-Bradley MicroLogix 1100 Specifications

General IconGeneral
Processor32-bit
Programming SoftwareRSLogix 500
MountingDIN rail or panel mount
Power Supply24V DC
TypeCompact PLC
Digital Inputs12
Digital Outputs8
Analog Inputs4 (depending on model)
Analog OutputsOptional with expansion module
Programming LanguageLadder Logic
Operating Temperature0 to 55 °C (32 to 131 °F)
SeriesMicroLogix