Publication 1763-RM001C-EN-P - October 2009
130 Using High-Speed Outputs
Jog Pulse (JP) bit must be off
Jog Continuous (JC) bit must be off
Enable Hard Stop (EH) bit must be off
Normal Operation (NS) bit must be off
The output cannot be forced
The rung it is on must transition from a False state (0) to a True state
(1).
Momentary Logic Enable Example
In this example, the rung state is a momentary or transitional type of
input. This means that the false-to-true rung transition enables the PTO
instruction and then returns to a false state prior to the PTO instruction
completing its operation.
If a transitional input to the PTO instruction is used, the Done (DN) bit
turns on when the instruction completes, but only remains on until the
next time the PTO instruction is scanned in the user program. The
structure of the control program determines when the DN bit goes off. So,
to detect when the PTO instruction completes its output, you can monitor
the Done (DN), Idle (ID), or Normal Operation (NO) status bits.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1100 and is the answer not in the manual?

Allen-Bradley MicroLogix 1100 Specifications

General IconGeneral
Processor32-bit
Programming SoftwareRSLogix 500
MountingDIN rail or panel mount
Power Supply24V DC
TypeCompact PLC
Digital Inputs12
Digital Outputs8
Analog Inputs4 (depending on model)
Analog OutputsOptional with expansion module
Programming LanguageLadder Logic
Operating Temperature0 to 55 °C (32 to 131 °F)
SeriesMicroLogix

Related product manuals