132 Using High-Speed Outputs
Standard Logic Enable Example
In this example, the rung state is a maintained type of input. This means
that it enables the PTO instruction Normal Operation (NO) and maintains
its logic state until after the PTO instruction completes its operation. With
this type of logic, status bit behavior is as follows:
The Done (DN) bit becomes true (1) when the PTO completes and
remains set until the PTO rung logic is false. The false rung logic
re-activates the PTO instruction. To detect when the PTO instruction
completes its output, monitor the done (DN) bit.
Stage 0 1 2 3 4 5 6 7 8 9 10 11 12
Rung State
Sub-Elements: Relative Timing
Normal Operation /NO
Accelerate Status /AS
Run Status /RS
Decelerate Status /DS
Enable /EN
Done /DN
Idle /ID
Jog Pulse /JP
Jog Continuous /JC
Start of PTO Start of PTO
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1100 and is the answer not in the manual?

Allen-Bradley MicroLogix 1100 Specifications

General IconGeneral
Processor32-bit
Programming SoftwareRSLogix 500
MountingDIN rail or panel mount
Power Supply24V DC
TypeCompact PLC
Digital Inputs12
Digital Outputs8
Analog Inputs4 (depending on model)
Analog OutputsOptional with expansion module
Programming LanguageLadder Logic
Operating Temperature0 to 55 °C (32 to 131 °F)
SeriesMicroLogix

Related product manuals