Rockwell Automation Publication 7000-UM202D-EN-P - May 2018 11
Preface
Commissioning Support
After installation, Rockwell Automation medium voltage support is
responsible for commissioning support and activities in the PowerFlex 7000
product line.
Phone: 519-740-4790
Option 1 for technical and option 4 for commissioning questions
MVSupport_technical@ra.rockwell.com or
MVSupport_services@ra.rockwell.com
Rockwell Automation support includes, but is not limited to:
• quoting and managing product on-site start-ups
• quoting and managing field modification projects
• quoting and managing customer in-house and on-site product training
ATTENTION: To keep arc resistant structural integrity, if applicable, the
following rules must be followed:
• The pressure relief vent may not be tampered with, and it is not to be used as
a step.
• No unapproved alterations can be made to the enclosure.
• All covers, plates, and hardware removed for installation or maintenance
purposes must be re-installed and properly secured. Failure to do so voids
the arc resistant structural integrity.
• Power cable entry points are to be treated as the boundary to a hazardous
location and must be sealed accordingly. Failure to do so voids the arc
resistant structural integrity.
• A plenum or chimney must be used to direct the arc flash energy to a suitable
location. Failure to do so voids the arc resistant structural integrity. See
publication 7000-IN007
.
• All wiring between the low voltage panel and the power cell must be routed
through a suitable cable gland to ensure flames and gases are not
transmitted into this area (as fitted from factory).
• The medium voltage doors must be properly secured using the handle
mechanism (if provided), the key interlock (if provided), and the door bolts.
Failure to do so voids the arc resistant structural integrity.