52 Rockwell Automation Publication 7000-UM202D-EN-P - May 2018
Chapter 2 Power Component Definition and Maintenance
6. Install the new capacitor, sliding it back until it fits into the slot. Fasten 
the front bracket.
7. Reconnect all the power cables and the ground connection. These use 
M14 hardware, but should only be tightened to 30 N•m (22 lb•ft) due 
to capacitor mechanical constraints. You may want to fasten these 
connections before fully sliding the capacitor into place depending on 
the available space.
8. Follow the instruction labels on each capacitor to tighten the terminal 
connections. 
9. Reinstall the removed sheet metal, and complete one final check to 
ensure connections are secure and correct.
Testing Filter Capacitors
There are two ways to test line filter capacitors. Rockwell Automation 
recommends the first method as it reduces the chance of re-torque issues 
because the capacitors are not disconnected. If the readings are unsatisfactory, 
the second method is more accurate, but involves disconnecting and testing 
them individually. 
First Method
1. Ensure there is no power to the equipment.
2. Follow appropriate safety steps to isolate the equipment from medium 
voltage.
3. Verify that there is no voltage present on the capacitor by using a hot 
stick or any other appropriate voltage-measuring device.
4. Perform visual inspection to ensure there is no oil leak or bulge in any of 
the capacitors.
ATTENTION: The porcelain bushings are extremely fragile and any force 
applied to the bushings can damage the seal between the bushing and the 
body causing potential leaks or chipping.
ATTENTION: To prevent electrical shock, disconnect the main power before 
working on the drive. Verify that all circuits are voltage-free using a hot stick 
or appropriate voltage-measuring device. Failure to do so may result in injury 
or death.
ATTENTION: Verify the load is not running due to process. A freewheeling 
motor can generate voltage that feeds back to the equipment.