144 Rockwell Automation Publication 7000-UM202D-EN-P - May 2018
Chapter 3 Control Component Definition and Maintenance
6. Reconnect all the connections removed in the previous steps.
7. Before reconnecting the mounting bracket, apply control power to the
unit and ensure the UPS is configured for the AS400 communication
protocol. See the manual that comes with the UPS for instructions.
8. Once this has been confirmed, install the mounting bracket.
Low Voltage Control Section
The low voltage control section houses all of the control circuit boards, relays,
operator interface terminal, DC/DC power supply, and most other low voltage
control components. See Figure 125
for a generic representation of a low
voltage tub arrangement.
Figure 125 - Low Voltage Tub Compartment
Analog Control Board
Tach Feedback
Circuit Board
Drive Processor
Module (DPM)
DC/DC
Power
Supply
Optical Interface Boards