Rockwell Automation Publication 7000-UM202D-EN-P - May 2018 137
Control Component Definition and Maintenance Chapter 3
Figure 119 - Terminal Locations on 600W AC/DC Power Supply (Cosel)
Output Calibration
Ensure the output of the supply is 56V DC
(1)
.
There is a potentiometer on the top of the power supply that adjusts the
56V DC
(1)
output for the power supply. Isolate the output of the power
supplies; multiple supplies in series will affect your measurements. With the
control power on and the output of the AC/DC Converter isolated from the
drive control, adjust the potentiometer until the output equals 56V DC
(1)
.
Perform this test on each power supply. When all adjustments are complete,
reconnect the power supply to the circuit and re-measure the output. Readjust
if necessary.
If it is not possible to maintain 56V DC
(1)
, the power supply may be faulty.
Terminal/Connections
Descriptions
(600W Cosel Power Supply)
Single Phase Input
DC Outputs
Control Signals
Air Flow
FRONT VIEW
P1-AC Input PIN# LABEL
AC (L) Live
AC (N) (1500 W only) Neutral (1500 W only)
NC No Connection
FG Earth
P2-DC Output PIN# LABEL
++56V
–+56V COMM
P3-Fail Output PIN# LABEL
CN1 1-2 Connected
3-4 Connected
5, 6, 7, 8, 9, 10 N/C
CN2 N/C
CN3 7 - Alarm
8 - Alarm GND
(1) 56V DC for Pioneer and Cosel model numbers -XRWAC and earlier. 57V DC for Cosel model numbers -XRWAD and newer.