EasyManua.ls Logo

Ampcontrol IPD - Page 48

Ampcontrol IPD
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ampcontrol Pty Ltd ABN 28 000 915 542
IPD USER MANUAL
IPDB014 Version 14 SEP/2020
Uncontrolled Copy - Refer to Ampcontrol Website for Latest Version
Page 48 of 96
APPROVED FOR EXTERNAL DISTRIBUTION
PROPERTY OF AMPCONTROL PTY LTD
NOT TO BE REPRODUCED IN PART
10.2.2 Motor Overload Characteristic
See “m-OL” Curves (Drawing IPDB019) and Motor Overload Functional Block Diagram (Drawing
IPDB035) in Appendix A Drawings.
The current protection type “m-OL” is used when a motor overload characteristic is required. This
protection scheme uses a thermal model of the motor to determine the tripping characteristic. Thermal
modelling is based on a thermal time constant of 30 minutes (time multiplier setting of 1.0 times). The
time multiplier can reduce this value to a minimum thermal time constant of 1.5 minutes (time multiplier
setting of 0.05 times).
The three measured phase currents are squared and added together to provide the heating input into
the thermal model, which is described by:
Where:
m is the time multiplier
h is 0 for ‘cold motor’ and 1 for ‘hot motor’
Note that unlike Very Inverse current protection, Motor Overload protection does not have strictly
defined tripping times. The curves and function above describe the boundaries of the trip time, where:
The hot curve corresponds to the trip time after the motor has been running at the selected full
load current indefinitely (which results in a thermal accumulation of 89%), and
The cold curve corresponds to the trip time when the motor starts with zero accumulated thermal
energy.
The actual tripping times will normally be between these bounds, depending on the time the motor has
been running and the load, and hence the accumulated thermal energy in the motor.
The motor manufacturer’s data should be consulted to select the time multiplier appropriate for the
motor being protected. Typically, the capacity of a cold motor is given at six times its rated current. The
IPD trip curves can be used to select the time multiplier, which best suits the motors overload capacity.
While the main contactor is closed, the cooling output from the thermal model is calculated to achieve
the necessary time constants.
When the main contactor is open a “Cooling Multiplier” is used to modify the basic time constant. This
can be used to account for the reduced cooling capacity while the motor is not running (when
applicable, e.g. fan-cooled motors). This multiplier is selectable at 0.2, 0.3, 0.4, 0.5, 0.8, 1.0, 2, 5, 10,
20, and 50 times.
When 0.2 times is selected the motor off cooling rate is reduced to 20% of the motor running cooling
rate. A selection of 1.0 times sets the motor-off cooling rate equal to motor running cooling rate. This
selection is appropriate where cooling is maintained even when the motor is stopped, eg water cooled
motors.

Table of Contents

Related product manuals