EasyManua.ls Logo

Ampcontrol IPD - Phase Current Balance; Transient Overreach Compensation

Ampcontrol IPD
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ampcontrol Pty Ltd ABN 28 000 915 542
IPD USER MANUAL
IPDB014 Version 14 SEP/2020
Uncontrolled Copy - Refer to Ampcontrol Website for Latest Version
Page 50 of 96
APPROVED FOR EXTERNAL DISTRIBUTION
PROPERTY OF AMPCONTROL PTY LTD
NOT TO BE REPRODUCED IN PART
10.4 Phase Current Balance
Phase current balance protection is selected via the “Cur Bal Trp” selection (See Section 13, User
Adjustable Settings). The current balance measurement is displayed on the Remote Display Module and
is calculated as:
𝐼
𝑏𝑎𝑙
=
𝑀𝐴𝑋 ∆ 𝐼 × 100%
𝐼
𝑎𝑣𝑒
Where:
I
ave
= Average of the 3 phase currents
MAXI = The maximum deviation of a phase current from the average
The trip level is selectable at 5%, 10%, 20%, 50% and off.
The phase current balance protection is inhibited until the average current exceeds both 20% of the
selected full load current and the selected balance trip level.
If the trip level is exceeded, a timer is triggered. If the imbalance remains above the set level for more
than two seconds the relay trips. The event log records “Ibal” to differentiate it from a true over-current
trip.
The status of the timer is displayed adjacent to the “Ibal” value (Level 5, Position 2). A trip condition
occurs when the timer reaches 100%.
10.5 Transient Overreach Compensation
Transient overreach is a phenomenon experienced by overcurrent relays where a measured AC signal is
offset by a decaying DC component (see figure below, taken from IEC 60255-151). The effect is typically
caused by a step change in the measured signal, such as at contact closure for a direct-online motor.
Figure 10.2: Transient Overreach During Contactor Closure (Source: IEC 60255-151)

Table of Contents

Related product manuals