Smoke Control Programs
5-30 Infinity Smoke Control Guide
TOC
Print “ ** Can Not Close Numeric List. ** “
Endif
Stop
File Explanation:
This program clears all Faults caused by equipment failures, Infinet
controllers being OffLine, or Self-Test failures.
The program sets the values in the DateTime arrays PlantTimer and
CtlrTimer equal to the system Time, thereby resetting them.
The program clears the CX9200 Status4 Self-Test failure indicator.
The program then searches through all of the CX9200 numerics. If the
numeric name ends in “.Fail” or “.OVRR”, it’s value is set to OFF. Since
the Self-Test failures (“.ST.Fail”) end with “.Fail”, they will get cleared.
This program is called by MAIN program when the CLEAR FAULTS
pushbutton on the FSCS is pressed. The CLEAR FAULTS pushbutton
will only be acknowledged if the Master Key is ON, therefore the faults
can only be cleared when the Master Key in ON.