Smoke Control Programs
5-38 Infinity Smoke Control Guide
TOC
• Run the ClearFaults program if it is not already running, and the
CLEAR FAULTS button on the FSCS is pressed.
• Run the weekly self-test program, SmokeSelfTest, if all of the
following conditions are met:
— The SMOKE.ALM numeric is OFF, indicating that the system is
not currently responding to an Alarm.
— The Weekday is Sunday Through Friday. If the system is not re-
sponding to an Alarm, the self-test will occur when Weekday =
Sunday.
—The Hour is between 0 and 4. If the system is not responding to
an Alarm, the self-test will occur when Hour = 0.
— The SelfTested flag is OFF, indicating that the system has not
been self-tested this week.
— The SmokeSelfTest program is not currently running.
•If Weekday is equal to Saturday, then set the SelfTested flag to
FALSE. Therefore the system will be ready to perform a self-test the
following week.
•Print the Time to the COMM3 Statusbar if the SmokeSelfTest
program is not running.
• Delay for 1 second, then Goto
MainLoop:
and repeat the sequence
again.