Smoke Control Programs
5-38 Infinity Smoke Control Guide
TOC
Run the ClearFaults program if it is not already running, and the
CLEAR FAULTS button on the FSCS is pressed.
Run the weekly self-test program, SmokeSelfTest, if all of the
following conditions are met:
The SMOKE.ALM numeric is OFF, indicating that the system is
not currently responding to an Alarm.
The Weekday is Sunday Through Friday. If the system is not re-
sponding to an Alarm, the self-test will occur when Weekday =
Sunday.
—The Hour is between 0 and 4. If the system is not responding to
an Alarm, the self-test will occur when Hour = 0.
The SelfTested flag is OFF, indicating that the system has not
been self-tested this week.
The SmokeSelfTest program is not currently running.
•If Weekday is equal to Saturday, then set the SelfTested flag to
FALSE. Therefore the system will be ready to perform a self-test the
following week.
•Print the Time to the COMM3 Statusbar if the SmokeSelfTest
program is not running.
Delay for 1 second, then Goto
MainLoop:
and repeat the sequence
again.
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Andover Controls Infinity and is the answer not in the manual?

Andover Controls Infinity Specifications

General IconGeneral
BrandAndover Controls
ModelInfinity
CategoryController
LanguageEnglish

Related product manuals