Smoke Control Programs
5-51 Infinity Smoke Control Guide
TOC
If INFINITY1 Zone1.EXH then
Rfan = On
Else
If INFINITY1 Zone1.PRS then
Rfan = Off
Else
If INFINITY1 Zone1.SMK then
Rfan = On ‘Exhaust
Else
If INFINITY1 Zone2.SMK or INFINITY1 Zone3.SMK ~
or INFINITY1 Zone4.SMK or INFINITY1 ~
STRWL.SMK then
Rfan = Off ‘ pressurize
Else
Rfan = Default.Rfan ‘ Normal HVAC Control
Endif
Endif
Endif
Endif
Endif
Endif
Goto DamperControl
DamperControl:
‘ Outside (Supply) Air Damper
If INFINITY1 AH1OADmp.OVR.Cls then
OADmp = -On
Else
If INFINITY1 AH1OADmp.OVR.Opn then
OADmp = On
Else
If INFINITY1 Zone1.EXH then
OADmp = -On
Else
If INFINITY1 Zone1.PRS then
OADmp = On
Else
If INFINITY1 Zone1.SMK then
OADmp = -On ‘ Exhaust
Else
If INFINITY1 Zone2.SMK or INFINITY1 Zone3.SMK ~
or INFINITY1 Zone4.SMK or INFINITY1 ~
STRWL.SMK then
OADmp = On ‘ pressurize
Else
OADmp = DefaultDmpr.OA ‘ Normal HVAC Control