EasyManua.ls Logo

Andover Controls Infinity - Page 134

Default Icon
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Smoke Control Programs
5-58 Infinity Smoke Control Guide
TOC
Else
If INFINITY1 Zone1.SMK or INFINITY1 Zone2.SMK ~
or INFINITY1 Zone3.SMK or INFINITY1 ~
Zone4.SMK or INFINITY1 STRWL.SMK then
OADmp = On ‘ pressurize a zone is in smoke
Else
OADmp = DefaultDmpr.OA ‘ Normal HVAC Control
Endif
Endif
Endif
Endif
Endif
Endif
Exhaust Air Damper
If INFINITY1 AH2EADmp.OVR.Opn then
EADmp = On
Else
If INFINITY1 AH2EADmp.OVR.Cls then
EADmp = -On
Else
If INFINITY1 Zone2.EXH or INFINITY1 Zone3.EXH or ~
INFINITY1 Zone4.EXH then
EADmp = On ‘Open damper exhaust required
Else
If INFINITY1 Zone2.PRS and INFINITY1 Zone3.PRS ~
and INFINITY1 Zone4.PRS then
EADmp = -On ‘Close damper all zones being pressurized
Else
If INFINITY1 Zone2.SMK or INFINITY1 Zone3.SMK or ~
INFINITY1 Zone4.SMK then
EADmp = On ‘ Exhaust, smoke on at least 1 floor
Else
If INFINITY1 Zone1.SMK or INFINITY1 STRWL.SMK ~
then
EADmp = -On ‘ pressurize smoke in Zone 1 or Stairs
Else
EADmp = DefaultDmpr.EA ‘ Normal HVAC Control
Endif
Endif
Endif
Endif
Endif
Endif
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Related product manuals