Smoke Control Programs
5-63 Infinity Smoke Control Guide
TOC
Sfan = DefaultFanPosn
Endif
Endif
Endif
Endif
Endif
Goto FanControl
File Explanation:
The stairwell fan is controlled by a set of nested “if-then-else
statements. The nested “if-then-elsestatements prioritize the control
modes as follows:
The FSCS overrides: ON-OFF
Automatic Smoke Control
Weekly Self-Test
The SmokeSelfTest program in the CX9200 performs the weekly self-
test by setting the value of DefaultFanPosn.