Smoke Control Programs
5-65 Infinity Smoke Control Guide
TOC
Else
VAVDmp = DefaultDmprPosn ‘ Normal HVAC Control
Endif
Endif
Endif
Endif
Endif
Endif
Goto VAVDamperControl
File Explanation:
The VAV damper is controlled by a set of nested “if-then-else
statements. The nested “if-then-elsestatements prioritize the control
modes as follows:
The FSCS overrides: OPEN-CLOSE
Automatic Smoke Control
HVAC control
The HVAC control is performed by setting the value of
DefaultDmprPosn.