EasyManua.ls Logo

Andover Controls Infinity - Page 147

Default Icon
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Smoke Control Programs
5-71 Infinity Smoke Control Guide
TOC
STRWL.SMK then
Damper = 0 ‘ pressurize Zone
Else
Damper = DefaultDmprPosn ‘ Normal HVAC Control
Endif
Endif
Endif
Endif
Endif
Endif
Goto VAVDamperControl
File Explanation:
The VAV damper is controlled by a set of nested “if-then-else
statements. The nested “if-then-elsestatements prioritize the control
modes as follows:
The FSCS overrides: OPEN-CLOSE
Automatic Smoke Control
HVAC control
The HVAC control is performed by setting the value of
DefaultDmprPosn.
In this example, setting the output to 0 will open the damper, and setting
the damper to 1 will close the damper.
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Related product manuals