Smoke Control Programs
5-7 Infinity Smoke Control Guide
TOC
FL4SADmp.Cls = SMKDMPRS Fl4.SASDmp.Cls
FL4RADmp.Opn = SMKDMPRS Fl4.RASDmp.Opn
FL4RADmp.Cls = SMKDMPRS Fl4.RASDmp.Cls
‘ Update Override Numerics
AHU1.OVRR = AHU1 OverrideOn
AHU2.OVRR = AHU2 OverrideOn
SMKDMPRS.OVRR = SMKDMPRS OverrideOn
Return
File Explanation:
This function sets the CX9200 numerics in the left column equal to the
Infinet controller points in the right column. The CX9200 numerics are
used to control their corresponding LED on the FSCS and to set the
“.OVRR” override fault numerics.