EasyManua.ls Logo

Andover Controls Infinity - Page 89

Default Icon
190 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Smoke Control Programs
5-13 Infinity Smoke Control Guide
TOC
If mid(InBuffer, SWS + 8, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH2RADmp.OVR.Cls = SwitchState
If mid(InBuffer, SWS + 9, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
FL4SADmp.OVR.Opn = SwitchState
If mid(InBuffer, SWS + 10, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
FL4SADmp.OVR.Cls = SwitchState
If mid(InBuffer, SWS + 11, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
FL4VAV.OVR.Opn = SwitchState
If mid(InBuffer, SWS + 12, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
FL4VAV.OVR.Cls = SwitchState
If mid(InBuffer, SWS + 13, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH2EADmp.OVR.Opn = SwitchState
If mid(InBuffer, SWS + 14, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH2EADmp.OVR.Cls = SwitchState
If mid(InBuffer, SWS + 15, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH2Rfan.OVR.On = SwitchState
If mid(InBuffer, SWS + 16, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
AH2Rfan.OVR.Off = SwitchState
If mid(InBuffer, SWS + 17, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
FL4RADmp.OVR.Opn = SwitchState
If mid(InBuffer, SWS + 18, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
FL4RADmp.OVR.Cls = SwitchState
If mid(InBuffer, SWS + 19, 1) = “A” and Main.Key then ~
SwitchState = On Else SwitchState = Off
Technical Manuals Online! - http://www.tech-man.com

Table of Contents