EasyManua.ls Logo

Areva FLUOKIT M24+ - Corrective maintenance; Replacement of the three HV fuses; Replacement of the VDS (Voltage Detection System - LV capacitors)

Areva FLUOKIT M24+
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
17.6 Corrective maintenance
C O R R E C T I V E M A I N T E N A N C E Levels
Replacements or modifications See chapter 1 2 3
Replacement of the three HV fuses 17.7 X X X
Replacement of the VDS (Voltage Detection System) 17.8 X X
17.7 Replacement of the three HV fuses
Intervention Duration Busbar Cables Load Break Switch Earthing switch
Normal 30 mins. de−energized de−energized open closed
Possible 30 mins. energized de−energized open closed
Locking out the Functional Unit
All locking−out operations must be
performed according to the particular
rules for the network concerned.
Tools required:
− leather gloves
Parts required:
− 3 fuses with the same reference
(verify values in accordance with the
transformer power)
The body of a fuse can
become very hot following a
short circuit.
Take standard precautions (wear
work gloves).
For an apparently single
phase fault, it is imperative
that all 3 fuses be replaced.
F Open the load break switch.
F Ensure that there is an absence
of voltage.
F Close the earthing switch.
F Remove the cable access panel.
F Take hold of the fuse by the
upper part.
F Pull the fuse towards the front.
This causes the upper current
supply terminal shell to open.
The latter will remain open.
F Lift the fuse up to free it from
the lower current supply
terminal.
F Similarly remove all 3 fuses.
F Fit the replacement fuses by
carrying out the instructions
in § 7.9.
17.8 Replacement of the VDS (Voltage Detection System − LV capacitors)
Intervention Duration Busbar Cables Load Break Switch Earthing switch
Normal 30 mins. de−energized de−energized open closed
Possible 30 mins. energized de−energized open closed
Locking out the Functional Unit
All locking−out operations must be
performed according to the particular
rules for the network concerned.
Tools required:
− 10 mm open−ended spanner
Parts required:
− 1 VDS of the same reference
NB: The calibre of the VDS is depen-
dent on the voltage range.

Table of Contents