Testing Your System
Digital Life User Manual | Page 59 of 62 ATT-UM-V1.1-201303
Device Procedure Results Notes
433MHz
Repeater
(SW-ATT-
RPTR4)
DLS in Test Mode
Note: By testing outlying
433MHz devices,
including Vanishing
Door/Window Sensors,
Recessed Door/Window
Sensors, Motion Sensors,
Glass Break Detectors,
Smoke Detectors and CO
Detectors, which
communicate through a
433MHz Repeater, you
are automatically testing
the 433MHz Repeater.
End-to-End Testing
Test each outlying
433MHz device one at
a time by executing the
following procedure:
o Arm the system in
the Armed-STAY
Mode
o Open/trip one device
o After the alarm has
been observed,
enter your Alarm
Panel PIN to cancel
the alarm and then
enter your Alarm
Panel PIN again to
clear the message
End-to-End Testing
For each device
Keypad LCD will display:
<Device Name> -
Opened or <PIR Device
Name> - Motion or
<Smoke Device Name>
- Smoke Detected or
<CO Device Name> -
CO Detected> <Device
Name> - Glass
Breakage (For example,
“Master Bedroom
Window - Opened”)
Keypad LCD will display:
Intrusion Alarm Sent or
Fire Alarm Sent or CO
Alarm Sent
Keypad LCD will
Display: Alarm – Enter
PIN to Cancel
Keypad LCD will display:
Alarm Canceled
Keypad LCD will display:
Enter PIN to Clear
An Intrusion Alarm
or Fire Alarm or
CO Alarm has
been sent to AT&T
Digital Life Central
Monitoring Center
with no action
required