7 Remote Control
Page 122 Mk8 MM Expansion Features Installation and Set-Up Guide 04.09.2016
Address Description Type
32051 External Level Sensor Reading Depth Read analogue
Metric: mm
Imperial: inches x 10
32052 Second Low Probe Input Read analogue
0 = No water is detected, 1 = water is detected
32053 Auxiliary High Water Input Read analogue
0 = Input not active, 1 = input active
32054 Auxiliary 1
st
Low Input Read analogue
0 = Input not active, 1 = input active
32055 Auxiliary 2
nd
Low Input Read analogue
0 = Input not active, 1 = input active
32056 Combined Water level Reading Depth Read analogue
Metric: mm
Imperial: inches x 10
40001 Remote Required Setpoint Read/write analogue
Metric: temperature
O
C, pressure Bar x 10, low pressure Bar x 100
Imperial: temperature
O
F, pressure PSI, low pressure PSI x 10
After 1 minute of no Modbus communications to the unit, the M.M. will ignore this required
value and use the required setpoint set on the M.M.’s status screen.
40121 Remote Firing Rate Read/write analogue
%
40131 must be set to 1 to change the firing rate remotely
40131 Remote Firing Rate Enable Read/write analogue
0 = Remote firing rate disabled, 1 = remote firing rate enabled