2 Expansion Options
04.09.2016 Mk8 MM Expansion Features Installation and Set-Up Guide Page 19
Exp
Option
Default Range Description
101 0 Modbus Baud Rate
The baud rate on the MM should be set the same as the baud rate used on
the external Modbus communication program.
0 9600 Baud
1 19200 Baud
102 0 Modbus Parity Setting
The parity on the MM should be set the same as the baud rate used on the
external Modbus communication program.
0 No parity
1 Odd parity
2 Even parity
103 1 Modbus Stop Bits Setting
The stop bits on the MM should be set the same as the baud rate used on
the external Modbus communication program.
1 1 stop bit
2 2 stop bits
104 1 Modbus Device ID
This ID is used to recognise the device on the external Modbus
communication program.
1 – 247
105 0 Binary Format
The binary format on the MM should be set the same as the baud rate used
on the external Modbus communication program.
0 Binary format
1 ASCII format
106 - Unused
107 - Unused
108 - Unused
109 - Unused
110 0 First Outs Function
If first outs are enabled, they will can be configured and labelled in
Commission mode and Online Changes. To tie the first outs interlock to the
MM’s safety stat, set option/ parameter 145.
0 Disabled
1 Enabled
111 - Unused
112 - Unused
113 - Unused
114 - Unused
115 - Unused
116 - Unused