Installing I/O Modules
Installation Handbook, AutroSafe Interactive Fire Alarm System, Release 3, 116-P-ASAFE-FA/DE,
Rev. J, 2011-12-06,
Autronica Fire and Security AS
3.10 Input Module, Monitored, BSE-310
Screw Terminal no. Signal
1 IN1 +
2 IN1 - (0V)
3 IN2 +
4 IN2 - (0V)
5 IN3 +
6 IN3 - (0V)
7 IN4 +
8 IN4 - (0V)
9 24 VBAT
10 0 VBAT
Schematics
Screw
terminal 1
Front view when mounted on rail
Screw
terminal 1
0
Input
2
1
2K
250-2000 Ohm
(Recommended value
is 470 Ohm)
Monitoring resistor
Signal resistor
V+
Sense
Signal
Terminal point 1, 3, 5, 7
0V
Terminal point 2, 4, 6, 8
0V
R