Introduction
Installation Handbook, AutroSafe Interactive Fire Alarm System, Release 3, 116-P-ASAFE-FA/DE,
Rev. J, 2011-12-06,
Autronica Fire and Security AS
1.4 Environmental Requirements
The equipment complies to environmental conditions of IEC-721-3-3
class 3k5.
Ambient temperature:-5 to +40 C
Degree of protection:IEC-529/IP30
1.5 Equipment List
The AutroSafe Fire Alarm Control Panel consists of the following:
BS-310/01: Operator front panel *, complete with:
BSR-310:Display Board with LCD
BSZ-310Operator Board
EAC-300Processor Board
Option:
BUP-310Printer
EAU-310LON Interface (BS-320 type)
EAU-321Serial Port Communication Board
EAU-330Ethernet Communication Board
BC-310/01:Controller rear cabinet
UEA-323:Cabinet (H=321 mm, W=315 mm, D=139 mm)
BSL-310:Communication Module
BSF-310:Connection Module
BSS-310:Power Module
BSS-103A/02: Power Supply
Options:
Batteries2 x 12V / 12Ah (maximum)
Modules:
BSD-310Loop Driver Module (127 addresses)
BSD-311High-power Loop Driver Module
BSB-310Output Module (4 relays, monitored)
BSJ-310Output Module (8 open collector outputs)
BSE-310Input Module (4 inputs, monitored)
BSE-320Input Module (8 inputs, galvanic isolated)
*
The Controller serves as a connection unit for Loop Driver
Modules, I/O modules and power supply only. The cabinet is thus
delivered with a black panel in front instead of the Operator Front
Panel.