EasyManuals Logo

Autronica AutroSafe Maritime Gas Detection User Manual

Autronica AutroSafe Maritime Gas Detection
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
General Description
System Description and Operation, AutroSafe Maritime Gas Detection, 116-P-BS420MG/XGB, Rev. E, 2019-12-10,
Autronica Fire and Security
Page 11
4.7 Detectors and Field Devices
4.7.1 Gas Detectors
IR point Gas Detectors etc. connect to PowerLoop modules, type
BSD-340, each of which are capable of handling up to a maximum of
15 detectors on each PowerLoop, depending on the power
consumption of the field equipment and the loop topology. The two-
wire PowerLoop provides intelligent communication and DC power to
the detectors.
4.7.1.1 IR Point HC Gas Detectors
The AutroPoint Maritime Gas Detector is fully integrated by means of
built-in intelligent interface featuring a self-test function. The detector
can transmit analogue information and can also provide maintenance
data.
4.7.1.2 Toxic Gas Detectors
AutroTox Gas Detectors are connected to the PowerLoop by means of
a 4-20mA interface unit, type BN-342. Hot swapable sensor cells for
various gas types.
4.7.1.3 Other 4-20 mA units
Any 4-20mA process transmitter unit can be connected to the
AutroSafe PowerLoop via an BN-342 unit. Intelligent detectors with
internal self-diagnostics are able to provide a general fault signal via
the 4-20mA signal transferal in case of a malfunction.
4.8 PowerLoop Driver BSD-340
4.8.1 Description
The PowerLoop Driver BSD-340 functions as a protocol converter
between AutroFieldBus and PowerLoop. It consists of a PowerLoop
interface for power and communication, and an AutroFieldBus
interface towards an AutroFieldBus Driver
(AutroSafe panel internal).
The PowerLoop is a two-wire bus capable of delivering 30VDC/ 100W
connected in ring topology and is galvanically isolated from the rest of
the system. The PowerLoop interfaces detectors and other loop units
including a 4-20mA interface.
The BSD-340/1 provides a service port which is used for
commissioning and maintenance.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica AutroSafe Maritime Gas Detection and is the answer not in the manual?

Autronica AutroSafe Maritime Gas Detection Specifications

General IconGeneral
BrandAutronica
ModelAutroSafe Maritime Gas Detection
CategorySecurity System
LanguageEnglish

Related product manuals