Disabling
System Description and Operation, AutroSafe Maritime Gas Detection, 116-P-BS420MG/XGB, Rev. E, 2019-12-10,
Autronica Fire and Security
Page 45
enabled manually, the detection zone will be indicated as enabled. If
the points are given different disablement times, the detection zone
will be automatically indicated as enabled when the first point is
enabled (i.e. when the point with the shortest disablement time is
enabled).
11.7 Disabling Fire Alarm Devices
When you disable a Fire Alarm Device (audible or visual indicator), the
output which controls the FAD will be disabled. The FAD will thus give
no audible indication.
You can disable a single unit (audible or visual indicator) / alarm
circuit, or all units (FADs) in a selected Alarm Zone.
A disablement time can be set. When the disablement time expires,
the FAD(s) will automatically be enabled. The single FAD or all FADs
in a selected Alarm Zone can also be enabled manually from the
Enable Menu.
11.8 Disabling Fire Alarm Routing Equipment
When you disable Fire Alarm Routing Equipment (FARE), the output
which controls such equipment will be disabled. In the event of an
alarm, no fire alarm signals / fault signals will be sent to the fire
brigade.
A disablement time can be set. When the disablement time expires,
the Fire Alarm Routing Equipment will automatically be enabled. The
equipment can also be enabled manually from the Enable Menu.
11.9 Disabling Outputs
When you disable outputs which control Fire Protection Equipment
(FPE), in the event of an alarm / fault, no signals will be sent to trigger
the equipment. You can disable a single output, or all outputs in the
Operation Zone.
A disablement time can be set. When the disablement time expires,
the outputs which control Fire Protection Equipment will automatically
be enabled. The outputs can also be enabled manually from the
Enable Menu.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica AutroSafe Maritime Gas Detection and is the answer not in the manual?

Autronica AutroSafe Maritime Gas Detection Specifications

General IconGeneral
BrandAutronica
ModelAutroSafe Maritime Gas Detection
CategorySecurity System
LanguageEnglish

Related product manuals