General Description
System Description and Operation, AutroSafe Maritime Gas Detection, 116-P-BS420MG/XGB, Rev. E, 2019-12-10,
Autronica Fire and Security
Page 16
4.10.5 Connection – Current Sink
4.11 Outputs
4.11.1 Programmable Digital Outputs in Panel (BSJ-310 Module)
Discrete open collector outputs can be used for hardwired signals.
BSJ-310 modules, which fit in any AutroSafe BS-420MG or Controller
BC-420 panel, can be used for this purpose. In addition 24V DC
relays can be supplied for each output, which will provide volt-free
contacts if required. Each BSJ-310 module has eight open collector
outputs. Any detector within an AutroNet network can control any
output within the same network.
Delayed action and voting can be programmed for these outputs. For
example such outputs can be used for digital signals to the Control
System (inputs).
4.11.2 Programmable EOL Monitored 24VDC Outputs (BSB-310)
End-of-line resistor monitored 24V DC outputs can be used to drive
horns, sirens, bells, beacon and strobes etc. The BSB-310 module
provides four 1A automatic fused outputs. Maximum load per module
is 3A in total. Any detector within an AutroNet network can control any
output within the same network. The BSB-310 outputs are specially
designed for sounders and bells, thus programming facilities include a
variety of options like;
SOLAS function (Safety Of Life At Sea)
Delayed action
Voting
Digital output, monitored