Panel Overview
System Description and Operation, AutroSafe Maritime Gas Detection, 116-P-BS420MG/XGB, Rev. E, 2019-12-10,
Autronica Fire and Security
Page 28
Alarms Fault
Yellow light when a fault is detected on one or more audible and visual indicators. The Fault indicator
will also have a yellow light. Blinking (not accepted) / Steady (accepted).
External Alarm Disabled
Steady yellow light when the signal to Fire Alarm Routing Equipment (FARE) has been disabled. The
Function Disabled indicator has also a steady yellow light.
External Alarm Fault
Yellow light when a fault is detected on Fire Alarm Routing Equipment (FARE). The Fault indicator
will also have a yellow light. Blinking (not accepted) / Steady (accepted).
Alarm Disabled
Steady yellow light when one or more audible and visual indicators are disabled. The Function
Disabled indicator has also a steady yellow light.
Detector Inhibit
Steady yellow light if any points are inhibited.
Local Mode
Blinking yellow light if contact to the presentation system is lost. The Fault indicator will also blink and
a fault message will be shown.
Both indicators will have a steady yellow light if the fault message is accepted. If a connection has
been lost and is repaired again, a fault message is shown and the fault message and both indicators
will blink until the fault is accepted, on which both indicators will be turned off and the fault will
disappear.
6.7.2 The Operator Section (lower left section)
Function Delayed
Steady yellow light indicates that Immediate Output Actioning has been disabled (manual operation in
Menu Mode), i.e. a delay period is active for audible and visual indicators or Fire Alarm Routing
Equipment (FARE). Configurable.