Panel Overview
System Description and Operation, AutroSafe Maritime Gas Detection, 116-P-BS420MG/XGB, Rev. E, 2019-12-10,
Autronica Fire and Security
Page 27
Fault
The yellow Fault Warning indicator shows the presence
of a fault within the operation zone of the operator
panel.
Blinking light
Unaccepted fault warnings exist.
Steady light
All fault warnings are accepted.
Function Disabled
Steady yellow light when one or more of the following
components within the operation zone of the operator
panel are in the disabled state:
function delayed
individual points
detection zones
alarm zones
Audible and visual indicators, Fire Alarm Routing
Equipment, Fire Protection Equipment and Fault
Warning Routing Equipment.
System Fault
Steady yellow light when a system fault within the
operating zone of the operator panel is present.
Testing
Steady yellow light when one or more detection zones
within the operation zone of the operator
panel have been manually set to the test state.
6.7 Indication Devices
6.7.1 Upper Section
Power
Steady green light when power is ON.
More Events
In the event of more than one alarm.
The red More Events indicator shows that several detection
zones within an operating zone are in the fire alarm state.
Blinking red light:
In the event of an alarm. The audible and visual indicators
are still in active state.
Steady red light:
The Silence Alarms button has been pressed. All audible
and visual indicators activated by the alarm are no longer
active. The control and indicating equipment still remain in
the alarm condition.
External Alarm Output
Steady red light when the message is sent to a remote
device.
ALARM
The red alarm indicator shows that one or more detection
zones within the operating zone of the Operator Panel are
in alarm state.
Blinking red light:
In the event of an alarm.
Steady red light:
All audible and visual indicators activated by the alarm
condition have been deactivated by operating the
Silence Alarms button. The control and indicating
equipment still remain in the alarm condition.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica AutroSafe Maritime Gas Detection and is the answer not in the manual?

Autronica AutroSafe Maritime Gas Detection Specifications

General IconGeneral
BrandAutronica
ModelAutroSafe Maritime Gas Detection
CategorySecurity System
LanguageEnglish

Related product manuals