System Menu
System Description and Operation, AutroSafe Maritime Gas Detection, 116-P-BS420MG/XGB, Rev. E, 2019-12-10,
Autronica Fire and Security
Page 52
13.6 Cancel Inhibited Points
In an alarm situation, an inhibited point will not signal alarms to
outputs, but only present alarms, prealarms and early warnings on all
panels and AutroCom as usual (see Service Menu, Inhibit Point,
chapter 15.1.1).
This menu allows you to globally cancel all inhibited points (global
override function), meaning that all outputs that are configured to be
activated in an alarm situation will be activated.
13.7 Day / Night Timers
13.7.1 Starting / Stopping Automatic Day / Night
Operation from the Control Panel
From the Control Panel, it is possible to Start or Stop the automatic
day / night operation in the System Menu. After activation (Start) of the
automatic day/night operation, the affected Operation Zones will be
set to their correct state (Disabled or Enabled Immediate Output
Actioning) according to the specified schedules.
After deactivation (Stop) of the automatic day/night operation, the
affected Operation Zones will be left in its current state in respect to
Disabled/Enabled Immediate Output Actioning
13.7.2 Overriding Automatic Day / Night Operation from the Control Panel
It is possible to override the automatic day / night operation from the
control panel by stopping the Day / Night Timers, and then issuing
Enable / Disable Immediate Output Actioning commands manually.