Enabling
System Description and Operation, AutroSafe Maritime Gas Detection, 116-P-BS420MG/XGB, Rev. E, 2019-12-10,
Autronica Fire and Security
Page 49
12.7 Enabling Fire Alarm Routing Equipment
When you enable Fire Alarm Routing Equipment (FARE), the output
which controls such equipment will be enabled. In the event of an
alarm, fire alarm signals may be sent to the fire brigade (configurable).
12.8 Enabling Outputs
When you enable outputs which control Fire Protection Equipment
(FPE), in the event of an alarm, signals will be sent to trigger the
equipment. You can enable a single output, or all outputs in the
Operation Zone.
12.9 Enabling Fault Warning Routing Equipment
When you enable Fault Warning Routing Equipment (FWRE), the
output which controls such equipment will be enabled. In the event of
a fault, fault warning signals will be sent to, for example, the security
firm.
12.10 Enabling Carriers
A Carrier is a loop unit hosting one or several subunits.
When you enable a Carrier manually or when a disablement time has
been set and expires, the Carrier itself and all its subunits (functions)
will be enabled - with the exception of subunits (functions) that have
been disabled from other disablement sources, for example, by means
of a disable input device. The subunits that have been disabled from
other sources must also be enabled by means of the same sources.
12.11 Enabling Immediate Output Actioning
When enabling Immediate Output Actioning, there will be no delay on
the actioning of outputs to Fire Alarm Devices (audible and visual
indicators) and/or Fire Alarm Routing Equipment (FARE) in zones
configured as Delayed Action Detection Zones, Delayed Coincidence
Detection Zones or SOLAS Detection Zones.
It is possible to enable immediate output actioning for all Day / Night
areas or for selected Day / Night areas.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica AutroSafe Maritime Gas Detection and is the answer not in the manual?

Autronica AutroSafe Maritime Gas Detection Specifications

General IconGeneral
BrandAutronica
ModelAutroSafe Maritime Gas Detection
CategorySecurity System
LanguageEnglish

Related product manuals