SENSOR PROGRAMMING
Figure 5: Analog Output Menu Map
3.5.1. TEACH 4 mA (0 V) and TEACH 20 mA (10 V)
The Tch4mA (Tch0V) and Tch20mA (Tch10V) options use targets to set the 4 mA (0 V) and 20 mA (10 V) to the desired setpoints. When using
the buttons, only one value needs to be set if the second value is valid. When using the remote input, both values must be set.
Navigate:MENU > A_OUT > Tch2Pt > Tch4mA (Tch0V) or navigate: MENU > A_OUT > Tch2Pt > Tch20mA (Tch10V)
Remote input:Available
Button Instructions
1) Present the target.
2) Access the TEACH mode and TEACH the sensor.
3) Repeat steps 1 to 2 for the other setpoint, if desired.
Remote Input Instructions
Action Result
Present the target. The target must be within the sensor's measurement range.
The target's analog output measurement and distance
measurement values display.
Action Result
Navigate: MENU > A_OUT > Tch2Pt > Tch4mA (Tch0V)
OR
Navigate: MENU > A_OUT > Tch2Pt > Tch20mA (Tch10V)
The selected TEACH mode and "Teaching" display
while the sensor is being taught.
TEACH Accepted
The new value is shown on the second line of the
display and flashes before it is saved and the sensor
returns to the parent menu.
TEACH Not Accepted
"FAIL" and a warning message display, and the
sensor returns to the parent menu.
MENU A_OUT
or
or
Go Back to Parent Menu
Select Menu Item
Press to Save Setting
Press and Hold to Go Back
to Run Mode
Adj20mA +12000mm
Adj4mA +00050mm
Tch4mA 50mm
Tch20mA 12000mm
Tch2Pt Tch20mA
Tch2Pt Tch4mA
WndSize +02000mm
Tch12mA 6000mm
TchMid Tch12mA
TchMid WndSize
Slope Negative
Slope Positive
LossSig 20.5 mA
LossSig Hold
LossSig 3.5 mA
A_OUT Adj4mA
A_OUT Adj20mA
A_OUT Tch2Pt
A_OUT TchMid
A_OUT Slope
A_OUT LossSig
Offset 0mm
TchMid Offset