Parameters
Application handbook Servo pump function V1 for BM5000
Document No.: 5.17002.02
69
of 76
6
177.200 Integral-action time 0
DS-support DINT 0 to 7200000 ms
Integral-action time 0 (Control difference < Actuating variable 1).
177.201 Integral-action time 1
DS-support DINT 0 to 7200000 ms
Integral-action time 1 (Control difference >Actuating variable 1 AND
Control difference < Actuating variable 2).
177.202 Integral-action time 2
DS-support DINT 0 to 7200000 ms
Integral-action time 2 (Control difference > Actuating variable 2 AND
Control difference < Actuating variable 3).
177.203 Integral-action time 3
DS-support DINT 0 to 7200000 ms
Integral-action time 3 (Control difference > Actuating variable 3 AND
Control difference < Actuating variable 4).
177.204 Integral-action time 4
DS-support DINT 0 to 7200000 ms
Integral-action time 4 (Control difference > Actuating variable 4).
177.205 Filter order pressure controller adaption
DS-support DINT 0 to 30000
Filter for interpolation of pressure control adaption.
177.206 Ramp up time pressure set value
DS-support DINT 0 to 4096 ms
Ramp up time for pressure ramp function generator of set values.
Ramp up time is related to a change from 0 Bar to maximum pressure.